Cable and Jumper Connections for Main Board and Adder Modules
10
Table 1: Connectors and Jumpers on the Main Fire Alarm Board
ICAC-306 Input Class-A Converter Adder Module
Figure 4: ICAC-306 Input Class-A Converter Adder Module
There are no jumpers or cables to set on this module, just wiring from the converter (wires are fixed here) to the
Main Fire Alarm Board.
Initiating circuits must be wired from the ICAC-306 module to the Main Fire Alarm board. For example, Initiating
circuit 1 positive (red) and negative (black) wires are connected to the positive and negative terminals (respectively)
of Initiating circuit 1 on the Main Fire Alarm Board. From the ICAC-306 converter Initiating circuits are wired out to
the devices from the positive and negative terminals marked DET OUT and the circuit return wires are brought back
to the converter module to positive and negative terminals marked DET RET.
JW1
Remove this jumper if PR-300 is connected.
P4
Cable from connector P1 of the RM-306 Relay Adder Module connects here. Otherwise
not used.
JW2 Remove this jumper if an RM-306 Relay Adder Module is used.
JW3 Removed all the time.
JW4 Normally short.
JW5
Normally open. Place jumper here and power down the panel (both AC power and
batteries). Then power up the panel again, the password is restored to the default after
system startup. Once the system has reset, REMOVE the jumper from the pins at JW5.
Leave normally open.
JW6
Normally open to BLOCK configuration via modem, PC with a UIMA converter module or a
CFG-300 Configuration Tool. Place jumper here to ALLOW any type of configuration.
BLK RED
BLK REDBLK REDBLK REDBLK R EDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 OUT+- DET4 OUT+- DET5 OUT+- D ET6 OUT+
- DET1 RET+- D ET2 R ET+- D ET3 R ET+- DET4 RET+- DET5 RET+- DET6 RET+
mounting hole for
#6-32 screws
All these pins comes with
red and black wires which
are connected to the
detection circuit on the
main fire alarm board. Red
is positive and black is
negative
ICAC-306
mounting hole for
#6-32 screws